0x1C8 - Profiler latching mode

Address

Name

Data Type

Access

Cyclic access

NVM

Value range

Default value

Units

0x1C8

Profiler latching mode

UINT16

RW

Yes

Yes

See below

64

-

This register allows to select when the set-points are processed by the profiler (positioning start condition).

The meaning of each bit in this parameter is described next.

Bit number

15

...76543

2

1

0


ReservedLatch for position profiler

Latch for velocity profiler

Latch for current profiler

Reserved

Latch for position interpolationLatch for velocity interpolationLatch for current interpolation 

In operation modes using the profiler module, set-points can be latched automatically or manually, which can be selected by setting each bit with:

  • Bit set to 0: Selected profiler mode is automatically latched by set-point change.
  • Bit set to 1: Selected profiler mode must be manually latched by controlword.

By default this register value is 64 => 0x0040 which means that only profile position mode requires the control word latch. This configuration is the expected one for CiA402.