0x517 - Current loop status

Address

Name

Data Type

Access

Cyclic access

NVM

Value range

Default value

Units

0x517

Current loop status

UINT32

RO

Yes

No

Data type

-

-

This register shows the status of the current control loops.

The meaning of each bit in this parameter is described next.

BlockCurrent D/B loop status
Bits3130...282726252423...2019181716
MeaningLoop enabledReservedDerating limiting latchingI2T limiting latchingUpper saturator active latchingLower saturator active latchingReservedDerating limitingI2T limitingUpper saturator activeLower saturator active
BlockCurrent Q/A loop status
Bits1514...121110987...43210
MeaningLoop enabledReservedDerating limiting latchingI2T limiting latchingUpper saturator active latchingLower saturator active latchingReservedDerating limitingI2T limitingUpper saturator activeLower saturator active

Note

The latching bits of the control loops status get reset whenever the power stage transitions to "operation enabled" state or whenever a current loop PID parameter is changed.

Warning

When the commutation modulation type parameter is set to Brushless DC or Brushed DC, only the current quadrature path is used. In this case, the Current D/B loop status bit field must be ignored.