Skip to main content
Skip table of contents

Electrical Tuning: Frequency Design

Introduction

After having a proper identification of the system plant, you can configure the control loop.

In this document you will see the most important parts of this wizard, and how to use it.

You have to perform minimum one plant model in the previous step. Otherwise, this step will be disabled.

This page is not available if trapezoidal commutation is selected.

Further technical information about how Current control loop works, click on here.

Overview of this page

There are 3 parts:

  • System configuration and verification (red).

  • Bode diagrams of magnitude and phase (blue).

  • Display and Control widgets (yellow).

System Configuration and Verification

There are 3 main subparts:

  • Plant model choice (orange).

  • Control Loop configuration (purple).

  • System verification (green).

Bode diagrams of magnitude and phase

You have two tabs:

  • Closed loop (recommended)

  • Open loop

Both tabs show the Gain and Phase in frequency domain.

The Closed Loop Transfer Function (CLTF) is the most common way to describe the control system in the frequency domain. The data is taken while the loop is closed, so all of the closed loop dynamics are captured in this transfer function. The gain of the CLTF is very close to unity at low frequency and rolls off at high frequency, with some amplification in between. The phase of the CLTF is near 0 at low frequency and near -180 degrees at high frequency. This curve is typically used to state the system’s “Bandwidth”.

The Open Loop, or “Loop” transfer function (OLTF) is representative of all the frequency dependent blocks that make up of the servo loop, meaning the control, the drive, the plant, and the sensor. The OLTF for some systems can be taken with the servo loop open, but in many cases it must be either derived from the Closed Loop, or taken with the loop closed, and done so using the test point. The OLTF can be found from the Closed Loop using the formula CLTF/(1-CLTF), where CLTF is the complex representation of the closed loop transfer function. The CLTF can be measured by driving the system with random or swept sine at In2 and measuring Out2/In2. The OLTF can be found by driving with In2, but measuring Out2/Out3. The open Loop and closed loop transfer function are shown below.

Plant model choice

Depending on the identification method used on previous page, Electrical tuning: identification, you should select the model you want to use to design your controller.

  1. If theoretical identification was used, the only option will be design from datasheet.

  2. If experimental identification was used, the only option will be design from estimated model.

  3. If both were used, both options will appear.

Loop adjustment

The main goal of this step is to adjust the loop parameters: Kp and Ki. You can get them and simulate their implications for the system without saving in the drive. You will be able to see these simulations in different plots.

Once you consider these parameters works properly, you can save them into the drive. You can see below several examples about how the closed loop behaves with different Kp's and Ki's.

Methods

In order to do that you have to choose which methodology you want to apply.

There are 3 methods:

  • Pole placement

  • Pole-zero cancelation

  • Manual

Pole-zero cancellation and Pole-placement are automatic methods that calculate the Kp an Ki. Manual is to adjust the parameters manually and see the frequential response.

If you need more details about these methods and how their parameters affect to your system, click on the link as the image below shows.

Pole placement

You will see the following in this part.

You can adjust Kp and Ki moving both sliders: Bandwidth and Damping ratio.

Go to How to tune - Bandwidth section and Damping section, for further information about these parameters.

Pole-zero cancelation

If you think you don’t need the Damping parameter, you can use this method using only the Bandwidth parameter.

Manual

Here, you can modify Kp and Ki directly without any without adding a calculation based on the desired bandwidth and damping.

Example

In the case of Pole-zero cancellation.

If you move the Bandwidth slider or directly you edit the its value directly, Kp and Ki parameters will be modified automatically.

The label under the slider indicates the stability of the system

Check the frequential response of your system and adjust the slider until the expected result is obtained. Also, you can compare the response of the controller values saved on the drive against the suggested new ones.

In the page How to tune inside MotionLab3, you can see some more information, if you don’t know how to analyze the different plots.

You have further information as well in the Terminal:

However, these loop parameters won’t be saved into your drive. You have to click on the button “Save to the Drive”.

In order to check if they are properly saved, you can see:

  • These parameters in the Control widget in green color.

  • Drive Saved Closed Loop plots change their shape like Suggested Closed Loop.

Verification

To compute it, just click on the “Verification” button.

In this step, the main goal is checking how your actual system works with the current controller saved on the drive.

Let’s continue the example before.

Example

In order to make a verification, you can follow the steps below:

  1. Modify the bandwidth value.

  2. Click on the “Save to the Drive” button.

  3. And click on the “Verification” button.

Finally we get a message below that tells us.

Charts are updated as well.

The terminal shows the quality (goodness) of the verification. This goodness compares the simulate results with the experimental ones.

Finally, some very specific applications, might require changing the excitation parameters. This can be done through the Advanced Options.

These options are the same as you configured previously at identification step. In fact, that values are linked, and the same identification used in identification is used at verification.

These parameters are:

  • Mode: In verification no mode can be selected, since the excitation on the current loop is always in current. See Section Automatic identification - Step 8 for further details.

  • Amplitude: The maximum current amplitude.

  • Offset: How many units increase or decrease the continue with respect to the zero level.

  • fmin: The minimum frequency that the plant is made.

  • fspacing: The resolution of the frequency.

  • fmax: The maximum frequency.

Finally, the simulation results are represented in closed-loop and open-loop.

In these charts there are no Experimental Closed Loop plots, just the estimated ones.

Finally, you can use two filters per signal for your system:

  • Two for the current reference

  • Two for the current feedback

You can enable/disable at Control widget.

You can find further information at Filters and Offset section.

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.