0x1011 - Restore default parameters
Index | Sub Index | Name | Data Type | Acc. | Pdo Map. | NVM | Value range | Default value | Units |
---|---|---|---|---|---|---|---|---|---|
0x1011 | 0x01 | Restore all parameters | UINT32 | RW | No | No | UINT32 | - | - |
0x1011 | 0x02 | Restore communication parameters | UINT32 | RW | No | No | UINT32 | - | - |
0x1011 | 0x03 | Restore application parameters | UINT32 | RW | No | No | UINT32 | - | - |
With this object the default values of parameters according to the communication profile, device profile, and application profile are restored.
Parameters cannot be restored if the drive is in operational state. Refer to CiA402 state machine for further information about drive states.
In order to avoid the restoring of default parameters by mistake, restoring is only executed when a specific signature is written to the appropriate SubIndex.
The signature that must be written is "load":
MSB |
|
| LSB |
---|---|---|---|
d | a | o | l |
0x64 | 0x61 | 0x6F | 0x6C |